Nuclear Power Station-Dukovany
Dieselgenerator Stations In Nuclear
Customer: CEZ
Location: Nuclear power plant Dukovany
Project description
The company provided as a main subcontractor total reconstruction of electrical system and control system for 12 dieselgenerator stations (DGS) that operate in safety mode as power supply backups in category II. Control system provides control of DGS in all operational modes on nuclear power station Dukovany. ZPA Industry integrated control system and visualisation systems using GE Fanuc products. For control and visualization was implemented SCADA system based on Cimplicity HMI Plant Edition software from GE Fanuc. As a control system ZPA Industry chose distributed DCS control system based on GE Fanuc Series 90-30 units. Design of entire control system for DGS in all possible operational modes has gone under thourough reliability examination. Control system includes two independent monitoring stations and twelve control systems (one for each DGS), that include three stations of fixed logic system 1A,1B, and 1C; six process stations 1Am, 1Bm, 2A, 2B, 3 and 4; one station for interfacing with backup failure signalization (SACO) and one operator's workstation. Each process station consists from processor module, communication modules and I/O modules.
Project summary
Total Cimplicity licences 14
Screen total 330
I/O Analog total 2122
I/O Digital total 14980
Basic bus scan 500ms
Number of process station 72
Technology description
Nuclear power station Dukovany consists from 4 power generation units equipped with Russian reactors VVER440. First two power generation units are grouped to s.c. MPU1 (Main Power Unit no. 1). The others power generation units are grouped to MPU2. Current technology of MPU1 includes 6 pcs of DGS from Yugoslavian manufacturers, actually from JUGO TURBINA and RADE KONCAR. Current technology of MPU2 includes also 6 pcs of DGS but from Polish manufacturers, actually from ZGODA and DOLMEL. Another electrical equipment was from Yugoslavian, Polish or Russian production.
Engine manufacturer: JUGO TURBINA
Type: 6ZL 40/48
Description: four-stroke, stationary diesel engine with supercharging and cooling of air
Rated power: 3000kW
Nominal speed: 500rpm
Generator manufacturer: RADE KONCAR
Rated power: 2800kW
Nominal voltage: 6300V at 50Hz
Power factor: 0,8
Nominal speed: 500rpm
Engine manufacturer: ZGODA
Type: -
Description: four-stroke, stationary diesel engine with supercharging and cooling of air
Rated power: 3300kW
Nominal speed: 600rpm
Generator manufacturer: DOLMEL
Rated power: 2800kW
Nominal voltage: 6300V at 50Hz
Power factor: 0,8
Nominal speed: 600rpm
Dates of commissioning
Project was realized in several stages according to the power station maintenance period schedule, only 25 days per one DGS was allowed.
Since 2002 we provide the service working in which they are made other requests for adjustments to the control system in accordance with the modernization of technology.